ESP Addressable and Conventional Fire Protection • www.espuk.com
96 zone addressable fire alarm panel supplied with 1 loop.
Expandable to 4 loops using additional MAGPRO96-L250’s.
A maximum of 250 devices can be connected to each loop.
96 Zones
Maximum 250 devices per loop
Memory Log: 10,000 events
Networkable up to 32 Panels
320 x 240 pixel touch screen display
Free programing software
Micro USB port for PC connection
Loop & battery calculator softwar
e included
Certified to EN54–2/4
MAGPRO96 - Addressable 96 Zone Fire Panel
MAGPRO96-L250
Single Loop Expander 250 Devices
Made in
EU
EN54
OUTPUTS 1 Sounder 24v DC @ 300mA
4 Programable Relays 110v ac @ 1A
2 Monitored Outputs 24v DC @ 300mA
1 Auxillary Output 24v DC @ 300mA
1 Fault Output 24v DC @ 300mA
ENVIRONMENT Working Temperature -5C TO +40C
Storage -10C TO 60C
Humidity 0 - 95%
Weight 4.2KG
Dimensions 456 x 350 x 125mm
INPUTS Loops 1 expandable to 4
Devices Per Loop 250
Protocol MAGPRO
POWER Mains Fail Consumption 285mA DC - 1 LOOP
360mA DC - 2 LOOP
435mA DC - 3 LOOP
510mA DC - 4 LOOP
Mains Supply 230V AC + - 10%
Max Loop Current 500mA DC
Backup 1x12V 17Ah