ESP MAG816 Dokumentacja Strona 23

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 32
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 22
MAG816 - Installation and Operation Manual 23
6.5 Sound Signal
• Short beeps - After pressing the and upon the initial start-up of the panel
Continuous beep - Fire and/ or Fault status. The signal can be stopped by pressing the
button, but the LED indication remains.
• Interrupted beep - After pressing the
button to enable/disable zones/sound-
ers and the
button to access “One Man” test mode of zones. The signal can
be stopped by pressing the
button, but the LED indication remains.
6.6 Service Modes
Zone Enable / Disable
Each zone of MAG816 can be enabled or disabled.
To disable a zone:
• Press
button: DISABLE/ ENABLE LED blinks.
The ZONE 1 LED blinks in yellow (2 blinks
per second) if ZONE 1 is enabled and
lights permanently if ZONE 1 is disabled.
• Press
button, until you reach
the zone which has to be disabled: The respective zone LED blinks in yellow
(2 blinks per second).
Press
button: The LED of the disabled zone lights
permanently in yellow.
Press
button: That will run the procedure for initial
start-up of the panel (item 6.1).
At this point the zone is disabled.
To enable a zone:
Press
button: DISABLE/ ENABLE LED blinks.
The ZONE 1 LED blinks in yellow (2 blinks
per second) if ZONE 1 is enabled and
lights permanently if ZONE 1 is disabled.
• Press
button until you reach
the disabled zone: The LED of the disabled zone lights
permanently in yellow.
• Press
button: The zone LED will start blinking in yellow
(2 blinks per second).
Press
button: That will initialize the start-up procedure
and introduce the changes (item 6.1).
At this point the zone is enabled.